Rooftop HVAC Unit Leaking Into a Commercial Ceiling: Curb, Drain or Roof?

Technicians inspect HVAC drain piping and curb flashing on a Naples commercial rooftop.

A rooftop unit leak into a commercial ceiling comes from one of three places: the roof curb and its flashing, the unit’s condensate drain and pan, or rain getting into the ductwork through the outside-air intake or cabinet. Rain-only leaks point to the curb, leaks in dry weather with the AC running point to condensate, and wind-driven storms that leave the duct insulation damp point to the intake. The ceiling stain usually shows up under a supply diffuser, not under the unit.

Why does a rooftop unit leak show up under the diffusers?

Every packaged rooftop unit sits on a roof curb, a raised steel frame around one of the largest holes in the roof. The supply and return ducts drop straight through that opening into the ceiling plenum below. Any water that gets past the curb flashing, overflows the unit’s drain pan or blows in through the intake has a clear path: it falls into the duct openings inside the curb, runs along the bottom of the supply trunk and comes out at the lowest diffuser or the first leaky duct seam.

That is why the stained ceiling tiles are often well away from the unit, sometimes in a tenant space that has never had a roof leak. On the flat single-ply and modified bitumen roofs over most strip plazas and commercial buildings, the curb is where membrane, metal flashing, sealant and the unit’s own gaskets all meet. That makes it the most complicated joint on the roof and the usual starting point for a rooftop HVAC leak in Fort Myers. New tiles under a diffuser will stain again unless someone follows the water back up the duct to that joint, which is why our commercial ceiling leak repair begins on the roof beside the unit rather than on a ladder under the stain. Tenants have their own work to do while the landlord handles the roof, starting with moving stock out from under a ceiling leak in a plaza store.

Curb, condensate or duct: which one is it?

Ask your maintenance staff or tenant three things: when it drips, what the weather was, and whether the unit was cooling. Those answers usually narrow an RTU leak to one row before anyone climbs a ladder.

What you see Most likely source Who fixes it
RTU leak only during or right after rain, unit on or off Curb flashing, membrane seam at the curb, failed curb gasket Commercial roofer, with the HVAC contractor if the unit must be lifted
Drips on dry, humid days while the unit is cooling Clogged condensate trap, cracked or rusted drain pan, drain line discharging back toward the curb Commercial HVAC contractor
Rooftop HVAC leak after wind-driven storms, damp insulation inside the duct Economizer or outside-air hood, missing cabinet panel or gasket Commercial HVAC contractor
Water at diffusers plus ponding around the curb on the roof Both: condensate or rain sitting against the curb flashing Roofer and HVAC contractor together

Two sources at once is common on older units. If the leaking rooftop unit has been patched more than once, assume nobody has looked at the whole curb.

What fails at the curb and flashing?

Behind most rain-only RTU leaks is the flashing detail. The membrane has to turn up the side of the curb, terminate under a metal counterflashing and stay sealed while the unit vibrates on top of it for years. In Fort Myers, that joint also takes summer roof surface temperatures that move the membrane and sealant every day, and afternoon storms from June through September that keep testing it. Common failures are open seams at the inside corners of the curb, shrunken or split sealant at the counterflashing, a curb that is too short for the insulation added during a reroof, and a gasket between the unit and the curb that has dried out or was damaged when the unit was set.

Many units in Lee County were also shifted, stripped of panels or reset after Hurricane Ian in September 2022, and some curbs were resealed in a hurry. A rooftop unit leak that started after storm repairs often traces back to that work. Ponding water around the curb is a warning sign too, since water sitting against the flashing for days will find any small opening.

Why would a rooftop unit leak in dry weather?

Because it is draining its own water. A rooftop AC leak in a dry week almost always means condensate. Commercial units run long hours here, and with outdoor dew points above 70 F for months, the coil sheds a steady stream of water into the drain pan. The pan sits under the coil inside the cabinet, and on most units the blower pulls air through it, so the pan is under suction. The condensate trap on the drain line has to be the right depth to overcome that suction. If the trap is missing, too shallow or plugged with slime, water stays in the pan and overflows into the cabinet and the supply duct.

Older steel pans rust through and drip straight into the supply opening, the most direct RTU leak path there is. Some drain lines discharge onto the membrane right beside the curb, which feeds ponding and slime. When the rooftop unit leaking into the ceiling has a condensate problem, the HVAC contractor fixes the trap, the pan or the line routing. A roofer will not find anything wrong with the roof.

How does rain get inside the ductwork?

Most commercial units have an economizer or an outside-air hood that brings fresh air into the cabinet. The hood is designed to shed rain, but a bent or missing rain hood, a torn filter or mist eliminator, or dampers that do not close fully will let wind-driven rain straight into the mixing section. Missing screws on a service panel, a panel left loose after maintenance or a gasket that has fallen out do the same thing. The giveaway is an RTU leak that appears only in storms from one direction, with damp insulation inside the duct and a dry roof around the curb.

Is the wet duct insulation a mold problem?

It can be. Many supply ducts are lined inside with fiberglass duct liner, and the trunk running through the ceiling plenum is often wrapped outside as well. Liner soaked by a rooftop AC leak and left wet in a building that runs cool and humid can support mold growth inside the duct, where nobody sees it until the smell reaches the space. The EPA’s mold guidance treats wet porous materials that cannot be dried quickly as candidates for removal, and duct liner usually falls into that group. Once the HVAC contractor has stopped the water, our crew handles HVAC and duct mold removal inside the system, and with soaked liner that usually means cutting it out.

Lay-in mineral fiber ceiling tiles under the diffusers are cheap to replace and should not be dried and reused once they sag or stain. The materials above them are a different story: wet duct wrap, wet batt insulation on the deck, drywall bulkheads and the framing of any hard ceiling. We meter those materials and dry them to IICRC S500 goals, and we document every reading for the claim. Open-deck buildings have no tiles to catch the first drips, so a leak over gym equipment lands directly on whatever sits below.

Which vendor do you call first, and what do you document?

Start with the people in the space. Rope off the wet area, put out wet-floor signs, move inventory and equipment, and keep staff and customers out from under sagging tiles or lights in the grid that have water on them. Have the HVAC contractor shut the unit off and lock it out if condensate is the likely source. Do not send untrained staff onto the roof, and nobody goes up during lightning. Roof edges, skylights and wet membrane are fall hazards, and OSHA’s fall protection rules apply to your maintenance crew too.

Then call the trade the RTU leak pattern points to, and if the evidence is mixed, get the roofer and the HVAC contractor on the roof at the same time so neither can blame the other’s side of the curb. CAT 3 Recovery does not repair roofs or HVAC equipment. We handle the commercial water damage loss itself: tile and insulation removal, drying, moisture mapping and the paperwork the adjuster will ask for. For the claim, keep photos with timestamps, the dates and times of each leak, the weather on those days, the trade reports naming the source, and our drying logs. Check the lease as well: in many commercial leases the tenant maintains the HVAC and the landlord maintains the roof, but yours decides.

If you have a rooftop unit leak in Fort Myers dripping into a tenant space, call CAT 3 Recovery at (239) 310-2638. We work around business hours where we can and give you readings you can hand straight to the owner and the insurer.

What property managers ask us when an RTU drips into a tenant space

Can the tenant stay open while the ceiling dries?

Often, yes, if the wet area can be sectioned off and nothing overhead is at risk of falling. Drying equipment can run in a roped-off zone, and work that makes noise or dust can be scheduled after hours. If water reached light fixtures, electrical in the ceiling or the sprinkler heads, the affected area stays closed until the right trade has checked it.

Why did the leak stop after the roofer sealed the curb, then come back in July?

Because the roofer may have fixed one of two sources of the rooftop HVAC leak. A sealed curb stops rain, but it does nothing for a condensate trap that plugs in the humid months when the unit runs hardest. If the second round of drips happens on dry days with the unit cooling, call the HVAC contractor, and tell them the curb was already resealed.

Should we replace only the stained ceiling tiles?

Replace the stained ones, but lift the tiles around them first. Water from a leaking rooftop unit running out of a duct seam or a diffuser can wet the insulation, the duct wrap and the tiles several feet away before anything shows on the face. A moisture meter on the surrounding tiles and on the materials above the grid tells you how far the water went.